

|
 |
 |
Maintaining
& Repairing Refrigeration Equipment
| As a refrigeration technician, you must
be able to maintain, service, and repair refrigeration equipment.
This phase of our course provides information on different
jobs that you may be assigned. It is not intended to be all
encompassing. Manufacturers also provide instruction manuals
to aid you in maintaining and servicing their equipment |
Servicing
Equipment
Repair and service work on a refrigeration system consists
mainly of containing refrigerant and measuring pressures accurately.
One piece of equipment is the refrigerant gauge manifold set
(fig. 1). It consists of a 0-500 psig gauge for measuring
pressure at the compressor high side, a compound gauge (0-250
psig and 0 to -30 inches of mercury) to measure the low or
suction side, and valves to control admission of the refrigerant
to the refrigeration system. It also has the connections and
lines required to connect the test set to the system. Depending
on test and service requirements, the gauge set can be connected
to the low side, the high side, a source of vacuum, or a refrigerant
cylinder. A swiveling hanger allows the test set to be hung
easily, and the three additional blank connections allow for
securing the open ends of the three lines when the gauge set
is not in use. There is always a path from the low-side and
high-side input to the low-side and high-side gauge.
Another important piece of equipment is the portable vacuum
pump--s a sealed unit consisting of a single-piston vacuum
pump driven by an electric motor. A vacuum pump is the same
as a compressor, except the valves are arranged so the suction
valve is opened only when the suction developed by the downward
stroke of the piston is greater than the vacuum already
in the line. This
vacuum pump can develop a vacuum close to -30 inches of
mercury, which can be read on the gauge mounted on the unit
(fig. 2). The pump is used to reduce the pressure in a refrigeration
system to below atmospheric pressure.
Various manufacturers manufacture hermetic refrigeration
systems used by the Navy; therefore, the connectors and
size of tubing vary. The Table of Allowance provides for
a refrigeration service kit that contains several adapters,
wrenches, and other materials to help connect different
makes of systems to the refrigerant manifold gauge set and
the vacuum pump lines. A table affixed to the lid of the
storage container identifies the adapter you should use
for a particular refrigeration unit.
Back to Top |
Transferring
Refrigerants
Refrigerants are shipped in compressed gas cylinders as a
liquid under pressure. Liquids are usually removed from the
shipping containers and transferred to a service cylinder
Before attempting transfer of refrigerants from a container
to a cylinder, pre-cool the receiving cylinder until its
pressure is lower than that of the storage container or
cylinder. Pre-cool by placing the cylinder in ice water
or a refrigerated tank. You must also weigh the service
cylinder, including cap, and compare it with the tare weight
stamped or tagged on the cylinder. The amount of refrigerant
that may be placed in a cylinder is 85 percent of the tare
weight (the weight of a full cylinder and its cap minus
the weight of the empty cylinder and its cap)
To transfer refrigerants, connect a flexible charging line
on a 1/4-inch copper tube several feet long with a circular
loop about 8 to 10 inches in diameter. Be sure to install
a 1/4-inch refrigerant shutoff valve in the charging line
to the service cylinder. This valve should be inserted so
no more than 3 inches of tubing is between the last fitting
and the valve itself. This arrangement prevents the loss
of refrigerant when the service drum is finally disconnected.
The entire line must be cleared of air by leaving the flare
nut on the service cylinder loose and cracking the storage
cylinder valve. This arrangement allows refrigerant to flow
through the tubing, clearing it. After clearing, tighten
the flare nut and then open the valve on the service cylinder,
the valve on the storage cylinder, and then the 1/4-inch
valve in the refrigerant line. When the weight of the service
cylinder shows a sufficient amount of refrigerant is in
the serviced cylinder, close all valves tightly, and disconnect
the charging line at the service cylinder
CAUTION - To warm refrigerant containers or cylinders for
more rapid discharge, use care to prevent a temperature
above 120°F because the fusible plugs in the cylinder
and valve have a melting point of about 157°F
Back to Top |
Evacuating
and Charging a System
Evacuation Before a system can be charged, all moisture
and air must be eliminated from the components by drawing
a vacuum on the system. To draw a vacuum on the system,
proceed as follows:
Connect
the portable vacuum pump to the vacuum fitting on the
refrigerant manifold gauge set
- Connect the LO line (suction) to the suction service
valve of the compressor, using appropriate connectors
if required
- Turn the suction service valve to mid-position, so vacuum
draws from the compressor crankcase and suction line back
through the evaporator, expansion valve, and liquid line.
When the receiver service valve, condenser service valve,
and discharge service valve are open, the pump draws back
through the receiver and condenser to the compressor
- Attach one end of a 1/4-inch copper tube to the vacuum
pump discharge outlet (Fig. 3). Allow the vacuum pump
to draw a vacuum of at least 25 inches. Submerge the other
end of the copper tubing under 2 or 3 inches of clean
compressor oil contained in a bottle
- Continue to operate the vacuum pump until there are
no more bubbles of air and vapor in the oil, which indicates
that a deep vacuum has been obtained
- Maintain the deep vacuum operation for at least 5 minutes,
and then stop the vacuum pump. Leaking discharge valves
of a vacuum pump cause oil to be sucked up into the copper
discharge tube. Keep the vacuum pump off at least 15 minutes
to allow air to enter the system through any leaks. Then
start the vacuum pump. A leaky system causes bubbling
of the oil in the bottle
- Examine and tighten any suspected joints in the line,
including the line to the vacuum pump. Repeat the test
Charging In most small refrigerating systems, low-side
charging (fig. 4) is generally recommended for adding refrigerant
after repairs have been made. After the system has been
cleaned and tested for leaks, the steps to charge the system
are as follows:
Connect
a line from a refrigerant cylinder to the bottom center
connection on the refrigerant gauge manifold set. Be certain
the refrigerant cylinder is in a vertical position, so
only refrigerant in the form of gas, not liquid, can enter
the system. Leave the connection loose and crack the valve
on the cylinder. This fills the line with gas and clears
the air from the line. After clearing, tighten the connection
- Connect a line from the LOW (LO) valve (suction) on
the gauge manifold set to the suction service valve of
the compressor
- Start the compressor
- Open the valve on the cylinder and the LOW (LO) valve
(suction) on the gauge manifold set
- Open the suction service valve on the compressor to
permit the gas to enter the compressor where it will be
compressed and fed to the high side. Add the refrigerant
slowly and check the liquid level indicator regularly
until the system is fully charged. It is easy to check
the receiver refrigerant level in some makes of condensing
units because the receiver has minimum and maximum liquid
level indicator valves which show the height of the liquid
level when opened. If a liquid line sight glass is used,
the proper charge may be determined when there is no bubbling
of refrigerant as it passes by the glass. The sight glass
will appear empty
Again, be certain the refrigerant cylinder is in the vertical
position at all times; otherwise, the liquid refrigerant will
enter the compressor and, liquid not being compressible, damage
the piston or other parts of the compressor.
Back to Top |
Refrigerant
Leaks
The best time to test joints and connections in a system is
when there is enough pressure to increase the rate at which
the refrigerant seeps from the leaking joint. There is usually
enough pressure in the high-pressure side of the system; that
is, in the condenser, receiver, and liquid line, including
dehydrators, strainers, line valves, and solenoid valves.
This is not necessarily true of the low-pressure side of the
system, especially if it is a low-pressure installation, such
as for frozen foods and ice cream, where pressures may run
only slightly above zero on the gauge. When there is little
pressure, increase the pressure in the low-pressure side of
the system by bypassing the discharging pressure from the
condenser to the low-pressure side through the service gauge
manifold Small leaks cannot be found unless the pressure inside
the system is at least 40 to 50 psi, regardless of the method
used to test for leaks.
Halide Leak Detector
The use of a halide leak detector is the most positive
method of detecting leaks in a refrigerant system using
halogen refrigerants (R-12, R-22, R-11, R-502, etc.). Such
a detector consists essentially of a torch burner, a copper
reactor plate, and a rubber exploring hose. Detectors use
acetylene gas, alcohol, or propane as a fuel. A pump supplies
the pressure for a detector that uses alcohol. If a pump-pressure
type of alcohol-burning detector is used, be sure that the
air pumped into the fuel tank is pure.
An atmosphere suspected of containing a halogen vapor is
drawn through the rubber exploring hose into the torch burner
of the detector. Here the air passes over the copper reactor
plate, which is heated to incandescence. If there is a minute
trace of a halogen refrigerant present, the color of the
torch flame changes from blue (neutral) to green as the
halogen refrigerant contacts the reactor plate. The shade
of green depends upon the amount of halogen refrigerant;
a pale green color shows a small concentration and a darker
green color, a heavier concentration. Too much of a halogen
refrigerant causes the flame to burn with a vivid purple
color. Extreme concentrations of a halogen refrigerant may
extinguish the flame by crowding out the oxygen available
from the air.
Normally, a halide leak detector is used for R-12 and R-22
systems. In testing for leaks always start at the highest
point of the system and work towards the lowest point because
halogen refrigerants are heavier than air.
When using a leak detector, you will obtain the best results
by following the Precautions listed below:
- Be sure the reactor plate is properly in place.
- Adjust the flame so it does not extend beyond the end
of the burner. (A small flame is more sensitive than a
large flame. If it is hard to light the torch when it
is adjusted to produce a small flame, block the end of
the exploring hose until the fuel ignites; then gradually
open the hose.)
- Clean out the rubber exploring hose if the flame continues
to have a white or yellow color. (A white or yellow flame
is an indication that the exploring tube is partially
blocked with dirt.)
- Check to see that air is being drawn into the exploring
tube; this check can be made from time to time by holding
the end of the hose to your ear.
- Hold the end of the exploring hose close to the joint
being tested to prevent dilution of the sample by stray
air currents.
- Move the end of the exploring hose slowly and completely
around each joint being tested. (Leak testing cannot be
safely hurried. There is a definite time lag between the
moment when air enters the exploring hose and the moment
it reaches the reactor plate; permit enough time for the
sample to reach the reactor plate.)
If a greenish flame is noted, repeat the test in the same
area until the source of the refrigerant is located.
Always follow a definite procedure in testing for refrigerant
leaks, so none of the joints are missed. Even the smallest
leaks are important. However slight a leak may seem, it
eventually empties the system of its charge and causes faulty
operation. In the long run, the extra time spent in testing
each joint will be justified. A refrigerant system should
never be recharged until all leaks are discovered and repaired.
Electronic Leak Detector
The most sensitive leak detector of all is the electronic
type. The principle of operation is based on the dielectric
difference of gases. In operation, the gun is turned on
and adjusted in a normal atmosphere. The leak-detecting
probe is then passed around the surfaces suspected of leaking.
If there is a leak, no matter how tiny, the halogenated
refrigerant is drawn into the probe. The leak gun then gives
out a piercing sound, or a light flashes, or both, because
the new gas changes the resistance in the circuit.
When using an electronic leak detector, minimize drafts
by shutting off fans or other devices that cause air movement.
Always position the sniffer below the suspected leak. Because
refrigerant is heavier than air, it drifts downward. Always
remove the plastic tip and clean it before each use. Avoid
clogging it with dirt and lint. Move the tip slowly around
the suspected leak.
Soap and Water Test
Soap and water may be used to test for leakage of refrigerant
with a pressure higher than atmospheric pressure. Make a
soap and water solution by mixing a lot of soap with water
to a thick consistency. Let it stand until the bubbles have
disappeared, and then apply it to the suspected leaking
joint with a soft brush. Wait for bubbles to appear under
the clear, thick soap solution.
Find extremely small leaks by carefully examining suspected
places with a strong light. If necessary, use a mirror to
view the rear side of joints or other connections suspected
of leaking.
Back to Top |
Pumping
Down
Quality refrigeration repair includes preventing loss of refrigerant
in the system. Whenever a component is removed from the system,
the normally closed system is opened and, unless precautions
are taken, refrigerant is lost to the atmosphere. The best
way to contain the refrigerant (gas and liquid) is to trap
it in the condenser and receiver by pumping down the system.
Connections for pumping down
a system
To pump down the system, proceed as follows:
- Secure electric power to the unit and connect the refrigerant
manifold test set, as shown in figure 5
- Close the receiver stop (king) valve (by turning the
valve stem inwards as far as it will go), and close both
gauges on the gauge manifold (LO and HI valves)
- Start the compressor and mid-seat the discharge and
suction service valves
- Operate the compressor until the pressure on the suction
(LO) gauge on the manifold shows a vacuum at 0 to 1 psi.
- Stop the compressor. If the pressure rebuilds appreciably,
operate the unit again until pressure registers between
0 to 1 psi. Repeat this step until the pressure no longer
rebuilds appreciably
- When suction pressure remains at about 0 to 1 pound
as read on the compound gauge, then front-seat the suction
and discharge service valves. This procedure traps practically
all the refrigerant in the condenser and receiver
Back to Top |
Recovery,
Recycling and Reclaiming Refrigerant
Laws governing the release of chlorofluorocarbon refrigerants
(CFCs) into the atmosphere have resulted in the development
of procedures to recover, recycle, and reuse these refrigerants.
Many companies have developed equipment necessary to prevent
the release of CFCs into the atmosphere. Refrigerant recovery
management equipment can be divided into three categories—recovery,
recycle, and reclaiming equipment.
Recovery
Removing refrigerant from a system in any condition and
storing it in an external container is called "recovery."
Removal of refrigerant from the system is necessary, in
some instances, when repair of a system is needed. To accomplish
this, you can use special recovery equipment, which is now
a requirement when removing refrigerant from a system. This
equipment ensures complete removal of the refrigerant in
the system.
Recovery is similar to evacuating a system with the vacuum
pump and is accomplished by either the vapor recovery or
liquid recovery method. In the vapor recovery method (fig.
6), a hose is connected to the low-side access point (compressor
suction valve) through a filter-drier to the transfer unit,
compressor suction valve. A hose is then connected from
the transfer unit, compressor discharge valve to an external
storage cylinder. When the transfer unit is turned on, it
withdraws vapor refrigerant from the system into the transfer
unit compressor, which, in turn, condenses the refrigerant
vapor to a liquid and discharges it into the external storage
cylinder.

The Vapor Recovery Method |

The Liquid Recovery Method |
In the liquid recovery method (fig. 7), a hose is connected
to the low-side access point to the transfer unit compressor
discharge valve. A hose is then connected from the transfer
unit compressor suction valve through a filter-drier to
a two-valve external storage cylinder. A third hose is connected
from the high-side access point (liquid valve at the receiver)
to the two-valve external storage cylinder. When the transfer
unit is turned on, the transfer unit compressor pumps refrigerant
vapor from the external storage cylinder into the refrigeration
system, which pressurizes it. The difference in pressure
between the system and the external storage cylinder forces
the liquid refrigerant from the system into the external
cylinder. Once the liquid refrigerant is removed from the
system, the remaining vapor refrigerant is removed using
the vapor recovery method as previously described.
Most recovery units automatically shut off when the refrigerant
has been completely recovered, but check the manufacturer's
operational manual for specific instructions. You should
make sure that the external storage cylinder is not overfilled.
Eighty percent capacity is normal. If the recovery unit
is equipped with a sight-glass indicator, any changes that
may occur should be noted.
Recycling
The process of cleaning refrigerant for reuse by oil separation
and single or multiple passes through filter-driers which
reduce moisture, acidity, and matter is called "recycling."
In the past, refrigerant was typically vented into the atmosphere.
Modern technology has developed equipment to enable reuse
of old, damaged, or previously used refrigerant. Refrigerant
removed from a system cannot be simply reused—it must
be clean. Recycling in the field as performed by most recycling
machines reduces the contaminants through oil separation
and filtration. Normally recycling is accomplished during
the recovery of the vapor or liquid refrigerant by use of
equipment that does both recovery and recycling of refrigerant.

Single-Pass Method of
Recycling |

Multi-Pass Method of Recycling |
Recycling machines use either the single-pass or multiple-pass
method of recycling. The single-pass method (fig. 8) processes
refrigerant through as filter-drier and/or uses distillation.
It makes only one pass through the recycling process to
a storage cylinder. The multiple-pass method (fig. 9) recirculates
refrigerant through the filter-drier many times, and after
a period of time or number of cycles, the refrigerant is
transferred to a storage cylinder.
Reclaiming
The reprocessing of a refrigerant to original production
specifications as verified by chemical analysis is called
"reclaiming." Equipment used for this process
must meet SAE standards and remove 100 percent of the moisture
and oil particles.
Most reclaiming equipment uses the same process cycle for
reclaiming refrigerant. The refrigerant enters the unit
as a vapor or liquid and is boiled violently at a high temperature
at extreme high pressure (distillation). The refrigerant
then enters a large, unique separator chamber where the
velocity is radically reduced, which allows the high-temperature
vapor to rise. During this phase all the contaminants, such
as copper chips, carbon, oil, and acid, drop to the bottom
of the separator to be removed during the "oil out"
operation. The distilled vapor then leaves the separator
and enters an air-cooled condenser where it is converted
to a liquid. Then the liquid refrigerant passes through
a filter-drier into a storage chamber where the refrigerant
is cooled to a temperature of 38°F to 40°F by an
evaporator assembly.
Back to Top |
Component
Removal or Replacement
To maintain a refrigerant system at a optimum operating condition
sometimes requires removal or replacement of some component.
Procedures for removal and replacement of some of the components
most often requiring action are covered in this section.
Removing Expansion or Float Valves
To help ensure good results in removing expansion or float
valves, you should pump the system down to a suction pressure
of just over zero. You should do this at least three times
before removing the expansion valve. Plug the opened end
of the liquid line and evaporator coil to prevent air from
entering the system. Repair or replace the expansion valve
and connect it to the liquid valve. Crack the receiver service
valve to clear air from the liquid line and the expansion
valve. Connect the expansion valve to the evaporator coil
inlet and tighten the connection. Pump a vacuum into the
low side of the system to remove any air.
Replacing an Evaporator
To replace an evaporator, pump down the system and disconnect
the liquid and suction lines. Then remove the expansion
valve and the evaporator. Make the necessary repairs or
install a new evaporator as required. Replace the expansion
valve and connect the liquid and suction lines. Remove moisture
and air by evacuating the system. When the evaporator is
back in place, pump a deep vacuum as in starting a new installation
for the first time. Check for leaks and correct them if
they occur. If leaks do occur, be certain to repair them;
then pump the system into a deep vacuum. Repeat the process
until no more leaks are found.
Removing the Compressor
Using the gauge manifold and a vacuum pump, pump down the
system. Most of the refrigerant will be trapped in the condenser
and the receiver. To remove the compressor from service,
proceed as follows:
- Once the pump down is complete, the suction valve should
already be closed and the suction gauge should read a
vacuum. Mid-seat the discharge service valve. Open both
manifold valves to allow high-pressure vapor to build
up the compressor crankcase pressure to 0 psi. Front-seat
(close) the discharge service valve.
- Then crack the suction service valve until the compound
gauge reads 0 to 1 psi to equalize the pressures and then
front-seat the valve.
- Joints should be cleaned with a grease solvent and dried
before opening. Unbolt the suction service and discharge
service valves from the compressor. DO NOT remove the
suction or discharge lines from the compressor service
valves.
- Immediately plug all openings through which refrigerant
flows using dry rubber, "cork" stoppers, or
tape.
- Disconnect the bolts that hold the compressor to the
base and remove the drive belt or disconnect the drive
coupling. You can now remove the compressor.
Removing Hermetic Compressors Systems using hermetic
compressors are not easily repaired, as most of the maintenance
performed on them consists of removal and replacement.
- Disconnect the electrical circuit including the overload
switch.
- Install a gauge manifold. Use a piercing valve (Schraider)
if needed.
- Remove the refrigerant using an EPA approved recovery/recycling
unit.
- Disconnect the suction and discharge lines.
- Using a pinching tool, pinch the tubing on both the
suction and discharge lines, and cut both lines between
the compressor and the pinched area.
- Disconnect the bolts holding the compressor to the base
and remove the compressor.
Do not forget to pump down the system and equalize the suction
and head pressure to the atmosphere, if applicable. Wear goggles
to prevent refrigerant from getting in your eyes. After replacement,
the procedures given for removing air and moisture and recharging
the system can be followed; however, the procedures may have
to be modified because of the lack of some valves and connections.
Follow the specific procedures contained in the manufacturer's
manual.
Back to Top |
|
|