

|
 |
 |
Maintaining
Motors
| Troubles with the electrical motors used
to drive the compressors of mechanical refrigeration systems
fall into two classes—mechanical and electrical. |
Mechanical
Problems
Some compressors are belt-driven from the electrical motor.
For proper operation, both the belt tension and pulley alignment
adjustments must be made. Belt tension should be adjusted
so a l-pound force on the center of the belt, either up or
down, does not depress it more than one-half inch. To adjust
the alignment, loosen the setscrew on the motor pulley after
tension adjustment is made. Be sure the pulley turns freely
on the shaft; add a little oil if necessary.
Turn the flywheel forward and backward several times. When
it is correctly aligned, the pulley does not move inward
or outward on the motor shaft. Tighten the setscrew holding
the pulley to the shaft before starting the motor.
Compressors may also be driven directly by a mechanical
coupling between the motor and compressor shafts. Be sure
the two shafts are positioned so they form a straight line
with each other.
The coupling on direct drive units should be realigned
after repair or replacement. Clamp a dial indicator to the
motor half coupling with its pointer against the outer edge
of the compressor half coupling. Rotate the motor shaft,
and observe any fluctuations of the indicator. Move the
motor or compressor until the indicator is stationary when
revolving the shaft one full turn. Secure the hold-down
bolts and then recheck.
Moisture in the System
When liquid refrigerant that contains moisture vaporizes,
the moisture separates from the vapor. Because the vaporization
of the refrigerant causes a cooling effect, the water that
has separated can freeze. Most of the expansion and vaporization
of the refrigerant occurs in the evaporator. However, a
small amount of the liquid refrigerant vaporizes in the
expansion valve, and the valve is cooled below the expansion
valve and interfere with its operation. If the needle in
the valve freezes in a slightly off-seat position, the valve
cannot permit the passage of enough refrigerant. If the
needle freezes in a position far from the seat, the valve
feeds too much refrigerant. In either case, precautions
must be observed to assure a moisture-free system.
A dehydrator is filled with a chemical known as a desiccant,
which absorbs moisture from the refrigerant passing through
the dehydrator. Dehydrators are installed in the liquid
line to absorb moisture in the system after the original
installation. An arrow on the dehydrator indicates the direction
of flow. Desiccants are granular and are composed of silica
gel, activated alumina, or calcium sulfate. Do not use calcium
chloride or chemicals that form a nonfreezing solution.
These solutions may react with moisture to form undesirable
substances, such as gums, sludges, or waxes. Follow the
manufacturer's instructions as to limitations of dehydrators,
as well as operation, recharging, replacing, and servicing.
Loose Copper Tubing
In sealed units, loose copper tubing is usually detected
by the sound of rattling or metallic vibration. Bending
the tubing carefully to the position of least vibration
usually eliminates the defect. Do not touch it against other
tubing or parts at a point of free movement, and do not
change the tubing pitch or the tubing diameter by careless
bending.
In open units, lengths of tubing must be well supported
by conduit straps or other devices attached to walls, ceilings,
or fixtures. Use friction tape pads to protect the copper
tubing from the metal of the strap. When two tubes are together
in a parallel position, wrapping and binding them together
with tape can prevent vibration. When two lines are placed
in contact for heat exchange, they should be soldered to
prevent rattling and to permit better heat transfer.
Doors and Hardware
When hinges must be replaced because of lack of lubrication
or other reasons, the use of exact duplicates is preferable.
Loose hinge pins must be securely braided. When thrust bearings
are provided, they are held in place by a pin.
The latch or catch is usually adjusted for proper gasket
compression. Shims or spacers may be added or removed for
adjustment. Latch mechanisms should be lubricated and adjusted
for easy operation. Latch rollers must not bind when operated.
Be sure to provide sufficient clearance between the body
of the latch and catch, so no contact is made. The only
contact is made between the catch and the latch bolt or
roller. These instructions also apply to safety door latches,
when they are provided for opening the door from the inside,
although it is locked from the outside. Warping of the door
usually causes lack of complete gasket contact between the
door overlap and the doorframe. Correct the condition by
installing a long, tapered wooden shim or splicer rigidly
in place under the door seal. If this does not tighten the
door to the frame, remove the door and either reline or
rebuild it.
Repair or replace missing, worn, warped, or loose door
gaskets. If the gasket is tacked on, rustproof tacks or
staples should be used. If the gasket is clamped or held
in place by the doorframe or the door panel, an exact replacement
is necessary. In either case, the gasket should be installed
so when the door is closed a complete and uniformly tight
seal results. If doors freeze closed due to condensation
and subsequent freezing, apply a light coat of glycerine
on the gaskets.
Defrosting
Cooling units in the 35°F to 45°F reach-in or walk-in
refrigerators or cold storage rooms are generally defrosted
automatically by setting the low-pressure control switch
to a predetermined level. If this setting causes overload
with consequent heavy frosting of the coil, manual defrosting
is necessary.
Cooling units of 35°F and lower temperatures are defrosted
manually. The most common method for manual defrosting is
to spray water over the cooling coil, although warm air,
electric heating, or hot gas refrigerant defrosts too. In
any case, the fans must not be in operation during the defrosting.
Defrost plate-type evaporator banks in below-freezing refrigerators
when the ice has built up to a thickness of one-half inch
or when the temperature of the fixtures or the suction pressure
is affected by the buildup of ice. Before removing frost
from the plates, place a tarpaulin on the floor or over
the contents of the refrigerator to catch the frost under
the bank.
Back to Top |
Electrical
Defects
The control systems for modern refrigeration systems are composed
of many components that use or pass electrical power, including
compressor drive motors, pressure switches, thermostats, and
solenoid stop valves.
Opens
An "open" is defined as the condition of a component
that prevents it from passing current. It may be a broken
wire, a burned or pitted relay contact, a blown fuse, a
broken relay coil, or a burned-out coil winding. An open
can be located in one of two ways.
For the components in series, such as the main disconnect
switch, fuses, the wire from Point C to Point D (fig. 1),
the relay contacts, and the wire from Point E to Point F,
a voltmeter should be used.
Set
up the voltmeter to measure the source voltage (120 volts
ac, in this case). If the suspected component is open, the
source will be measured across it. To check part of the
main disconnect switch, close the switch and measure from
Point A to Point B. If the meter reading is 0 volts, that
part of the switch is good; if the voltage equals the source
voltage, the switch is open.
To check the fuse F2, measure across it, Point B to Point
C. Measuring across Points C and D or E and F will check
the connecting wires for opens. One set of relay contacts
can be checked by taking meter readings at Points
D and E. These are just a few examples, but the rule of
series components can always be applied.
Remember, the three sets of contacts of relay K1 will not
close unless voltage is present across the relay coil; the
coil cannot be open or shorted. When testing an electrical
circuit, follow the safe practices you have been taught
and use procedures outlined in equipment manuals.
Opens in components that are in parallel cannot easily
be found with a voltmeter because, as you know, parallel
components have voltage across them at all times when the
circuit is energized. In figure 6-62, the branch with the
motor relay K1 and the dual refrigerant pressure control
are considered a parallel circuit.
Because when the main disconnect switch is closed and the
fuses are good, there is voltage between Points C and H,
regardless of whether the relay coil and pressure switch
are open. To check for opens in these components, use an
ohmmeter set at a low range.
Disconnect all power by opening (and locking out, if possible)
the main disconnect switch. This action removes all power
and ensures both personal and equipment safety. To check
the motor relay K1 to see if its coil is open, put the ohmmeter
leads on Points C and G. A reading near infinity (extremely
high resistance) indicates an open. The contacts of the
dual refrigerant pressure control can be tested by putting
the ohmmeter leads from Point G to Point H. Again, a reading
near infinity indicates open contacts. You may need to consult
the manufacturer's manual for the physical location of Points
G and H. Notice the contacts of the control are normally
closed when neither the head pressure nor the suction pressure
is above its set limits.
Shorts
Shorts are just the opposite of opens. Instead of preventing
the flow of current, they allow too much current to flow,
often blowing fuses. The ohmmeter on its lowest range is
used to locate shorts by measuring the resistance across
suspected components. If the coil of the motor relay K1
is suspected of being shorted, put the leads on Points C
and G. A lower than normal reading (usually almost zero)
indicates a short. You may have to determine the normal
reading by consulting the manufacturer’s manual or
by measuring the resistance of the coil of a known good
relay. If fuses F2 and F3 blow and you suspect a short between
the middle and bottom lines (fig. 6-62), put the ohmmeter
leads between Points C and H. Again, a low reading indicates
a short.
Remember, in all operations using an ohmmeter, it is imperative
that all power be removed from the circuit for equipment
and personal safety. Don't fail to do this!
Grounds
A ground is an accidental connection between a part of
an electrical circuit and ground, due perhaps, to physical
contact through wearing of insulation or movement. To locate
a ground, follow the same procedure you used to locate a
short. The earth itself, a cold-water pipe, or the frame
of a machine are all examples of ground points. To see whether
a component is shorted to ground, put one ohmmeter lead
on ground and the other on the point suspected to be grounded
and follow the rules for locating a short.
Be sure to turn off all power to the unit. It may even
be wise to check for the presence of voltage first. Use
a voltmeter set to the range suitable for measuring source
voltage. If power does not exist, then use the ohmmeter.
The limited amount of instruction presented here is not
enough to qualify you as an electrician, but it should enable
you to find such troubles as blown fuses, poor electrical
connections, and the like. If the trouble appears more complicated
than this, call your supervisor or ask for assistance from
a Construction Electrician.
Testing the Motor
As a refrigeration technician, you should be able to make
voltage measurements in a refrigeration system to ensure
the proper voltage is applied to the drive motor, as shown
on the rating plate of the motor. If the proper voltage
is applied (within 10 percent) to the terminals of the motor
and yet it does not run, you must decide what to do. If
it is an open system (not hermetically sealed), it is the
electrician's job to repair the motor. If it is a hermetically
sealed unit, however, you must use special test equipment
to complete further tests and perhaps make the unit operational
again.
If the unit doesn't run, it may be because the motor rotor
or compressor crankshaft is stuck (remember, in a hermetically
sealed unit, they are one and the same). If you apply electrical
power to try and move the motor in the correct direction
first and then reverse the power, you may be able to rock
it free and not have to replace the unit. This is one of
the purposes of the hermetic unit analyzer.
To rock the rotor of an hermetically sealed unit, follow
these steps:
- Determine from the manufacturer's manual whether the
motor is a split-phase or a capacitor-start type.
- Remove any external wiring from the motor terminals.
- Place the analyzer plugs in the jacks of the same color.
If a split-phase motor is used, put the red plug in jack
No. 3; if the capacitor-start motor is used, put the red
plug in jack No. 4; and select a capacity value close
to the old one with the toggle switches.
- Connect the test clips as follows: White to common Black
to the running winding Red to the starting winding
- Hold the push-to-start button down and at the same time
move the handle of the rocker switch from normal to reverse.
The frequency of rocking should not exceed five times
within a 15-second period. If the motor starts, be certain
that the rocker switch is in the normal position before
releasing the push-to-start button.
- More tests can be made with the hermetic unit analyzer,
such as testing for continuity of windings and for grounded
windings.
Procedures for these tests are provided in the manual that
comes with the analyzer.
Generally, if the rocking procedure does not result in
a free and running motor, the unit must be replaced.
Back to Top |
Troubleshooting
Refrigeration Equipment
Troubleshooting of any type of refrigeration unit depends,
in part, on your ability to compare normal operation with
that obtained from the unit being operated. Obviously for
you to detect these abnormal operations, you must first know
what normal operation is. Climate affects running time. A
refrigeration unit generally operates more efficiently in
a dry climate. In an ambient temperature of 75°F, the
running period usually approximates 2 to 4 minutes, and the
off period, 12 to 20 minutes.
It is beyond the scope of this text to cover all of the
troubles you may encounter in working with refrigeration
equipment. If you apply yourself, you can acquire a lot
of additional information through on-the-job training and
experience and studying the manufacturer's instruction manuals.
First and foremost, safety must be stressed and safe operating
practices followed before and while doing any troubleshooting
or service work. All local and national codes concerning
safety must be observed. Some of the more important safety
steps that are often overlooked are as follows:
- Protective equipment, such as eye protection, gloves,
hard hats, and so forth, must be available and worn.
- Fire extinguishers must be readily available, in good
working order, and adequate for the situation.
- Safety tags with such notations as "Danger,"
"Hands Off," "Do Not Operate," and
"Do Not Throw Switch" should be attached to
valves, switches, and at other strategic locations when
servicing or making repairs.
- Install machinery guards properly before operating machinery.
Back to Top |
|
|