Commercial Refrigeration
The general purpose of a refrigeration system is to cool and store
food and thereby preserve its shelf life. This is accomplished by
removing heat energy from the low temperature storage condition
(i.e. the heat source) and transferring this heat energy to a higher
temperature medium (i.e., the heat sink) usually outdoor air.
Other examples of refrigeration are:
- Holding and displaying perishable food.
- Chilling liquid for process cooling (common in the food processing
industry) and possibly to make hot water
(to provide heat for air handler heating or reheat. Supermarkets
routinely use this last concept.
- Chilling brine to freeze an ice sheet (e.g., a hockey arena).
- Heat pump systems (please see the separate section covering
heat pumps in more detail.
Refrigeration is only a means to an end. In most cases, that
end is the preservation of foods. Refrigeration is often a significant
steady use of year-round electricity since this equipment runs
even when the building is unoccupied. Therefore, it is usually
cost effective to install the most efficient refrigeration practical.
Consequently, utility representatives work closely with consumers
during the early planning stages to help consumers understand
their options. They will be alert to consumer expansion needs
and the potential replacement of old inefficient equipment with
new, improved units.
Refrigeration - Basic
Cycle Concepts
Heat energy always flows naturally from a higher to a lower temperature
level. That is, hot areas naturally cool off and cold areas naturally
warm up. Therefore, moving heat from a lower to a higher temperature
requires the input of work (or heat), usually to create a pressure
differential in the cycle refrigerant.
The refrigerant (acting as a heat transfer fluid) is used to
transfer heat energy from a lower temperature to a higher temperature.
The refrigerant is evaporated at a temperature lower than the
desired temperature in the freezer or cooler. The condensing temperature
of the refrigerant is increased by compression so that it can
either be rejected to the environment or recovered as useful heat.
The basic refrigeration cycle, with all steps combined, is shown:
Step
One, Evaporation: Liquid refrigerant at a sufficiently low
pressure is brought into contact with the heat source (the medium
to be cooled). The refrigerant absorbs heat and boils, producing
a low-pressure vapor. The heat exchanger used for this process
is called the evaporator.
Step Two, Compression: The compressor raises the pressure
of the refrigerant vapor, normally using an electric motor drive.
This increases the temperature at which the vapors will condense
to a temperature above the temperature of the heat sink. Most
common compressors are reciprocating (piston and cylinder) or
screw (looking much like an old meat grinder) compressor designs.
Step Three, Condensing: The high-pressure refrigerant
gas now carrying the heat energy absorbed at the evaporator plus
the work energy from the compressor, enters the condenser. Since
the refrigerant's condensing temperature is higher than that of
the heat sink, heat transfer will take place, condensing the refrigerant
from a high-pressure vapor to a high-pressure liquid.
Step Four, Expansion: The condensed liquid's pressure
is reduced (called "throttled") to the lower pressure evaporator
using a valve, orifice plate or capillary tube device. In actual
practice, the condenser cools the refrigerant a bit more, sub-cooling
it below the condensing temperature. This is an important efficiency
improving attribute to the cycle, since it reduces the amount
of refrigerant liquid that has to evaporate (it is called flashing
at this stage in the cycle) to a gas in the expansion valve to
reduce the pressure and temperature of the liquid entering the
evaporator. This reduction in flash gas is important to improve
system performance.
Back to Top
Energy Use Characteristics
of Refrigeration
Refrigeration cycles transfer thermal energy continually from a
region of low temperature to one of higher temperature. The higher
temperature heat sink is usually ambient air or cooling water. This
table lists some typical energy use data.
Typical Refrigeration Energy
Use (KW/TON) and COPS
| Compressor Size and Type Operating Temperatures |
| Large, over 25hp (19kW) |
| Evaporator: |
-40F |
0F |
40F |
45F |
| Condenser: |
105F |
110F |
100F |
130F |
| Open |
kW/Ton: |
3.5 |
1.9 |
0.8 |
1 |
| COP: |
1 |
1.8 |
4.4 |
3.5 |
| Hermetic |
kW/Ton: |
3.8 |
2 |
0.9 |
1.2 |
| COP: |
1.7 |
3.9 |
2 |
9 |
| Medium, 5 to 25hp (4-19 kW) |
| kW/Ton: |
3.9 |
2 |
0.9 |
1.1 |
| COP: |
0.9 |
1.7 |
3.9 |
3.2 |
| kW/Ton: |
4.2 |
2.1 |
1 |
1.3 |
| COP: |
0.8 |
1.7 |
3.5 |
2 |
| Small, under 5hp (4 kW) |
| kW/Ton: |
- |
- |
- |
- |
| COP: |
- |
- |
- |
- |
| kW/Ton: |
- |
3.2 |
1.2 |
1.5 |
| COP: |
- |
1.1 |
2.9 |
2.3 |
|
Back to Top
Refrigeration System
Operating Characteristics
Refrigeration systems must operate at all hours of the year, even
when the building is unoccupied. Warmer weather tends to push refrigeration
equipment to its capacity limit, thus creating a maximum operating
kW and kWh.
Evaporators - must be selected to provide the required
cooling at all expected ambient conditions even with the maximum
frost on the coils (i.e., just prior to defrosting). Evaporator
coils used include two types of refrigeration systems: flooded
evaporator and direct expansion. For direct expansion systems,
two of the most commonly used refrigerant liquid metering devices
are the capillary tube and the thermostatic expansion valve.
In addition, proper provisions must be made for periodic defrosting
of evaporator air-side surfaces. Defrosting may be accomplished
using refrigerant compressor discharge hot-gas, water spray, or
manually as selected to meet the user's objectives. Suitable drain
connections should be provided to carry off the water resulting
from defrost operations.
Condensers
- must be selected to operate at all outdoor weather conditions
in the area. Air-cooled condensers must be supplied with the proper
controls to permit operation at low outdoor ambient conditions.
Water-cooled condensers may require water regulating valves to
keep condensing pressure high enough to enable the thermal expansion
valves to function. The type of condenser selected depends largely
on the size of the cooling load, refrigerant used, quality and
temperature of available cooling water (if any), and noise considerations.
Water-cooled condensers require cooling water from an external
cooling tower, or from a lake, well, river or other similar source.
Once-through use of city water for condensing purposes is prohibited
in most locations. Air-cooled condensers are the most popular
since they avoid other problems of water acquisition, treatment
and disposal. The trade-off may be higher electrical consumption.
As seen here, the evaporative condenser is a combination of a
water cooled condenser and an air-cooled condenser that rejects
heat through the evaporation of water into an airstream traveling
across a condenser coil.
Compressors - must be sized to meet the varying needs
of each application. Provision must be made to protect the compressor
from liquid carry over from the evaporator, in addition to the
normal safety controls (high and low pressure cutout. oil pressure,
etc.). The most common type of compressor used for commercial
refrigeration systems is the reciprocating compressor. Reciprocating
compressor types include single-stage (booster or high state),
internally compounded, and open, hermetic or semi-hermetic.
Back to Top
CFC Issue
CFCs and the ozone layer - The ozone layer in the upper atmosphere
absorbs much of the ultraviolet light from the sun and, in so doing,
shields us from its harmful effects. Ozone in the lower atmosphere
(formed by the sun's action on air pollutants resulting in smog)
is harmful. Ozone in the earth's upper atmosphere acts as a protective
shield while ozone at the surface is undesirable.
Some scientists believe CFCs are contributing to deterioration
of the ozone layer. The theory is this: CFCs are extraordinarily
stable compounds that they do not break down in the lower atmosphere.
Although heavier than air traces of CFCs have been found in the
upper atmosphere where they have been predicted to last for 100
years or more. Affected by ultraviolet radiation, these CFC traces
slowly decompose and release chlorine. Chlorine (Cl2) with the
presence of sunlight is known to catalytically decompose ozone,
an oxidizer. The catalyzation of ozone forms chlorine oxide (which
is unstable) and produces oxygen. The unstable chlorine oxide
then breaks down to again form chlorine, and produce oxygen. This
process keeps repeatedly attacking the ozone. With the looping
process described it is believed that a single chlorine atom may
be able to destroy as many as 100,000 ozone molecules.
Volcanic eruptions and other (such as lightning) massive releases
of chlorine by Mother Nature play a role in the observed fluctuations
in the ozone layer. Scientists are in general agreement, however,
that CFCs have a negative effect on the ozone layer.
Because the potential detrimental effects of chlorine containing
refrigerants on the ozone layer, a world body was convened, with
several follow-on reviews. As a result these steps have been taken
to reduce consumption (production plus imports minus exports)
and implement phase-out.
Refrigerant Phase-out Schedule
| Refrigerant |
Year |
Restrictions |
| CFC-11 |
1996 |
Ban on production |
| CFC-12 |
1996 |
Ban on production |
| HCFC-22 |
2010 |
Production freeze and ban on use in new equipment |
| 2020 |
Ban on production |
| HCFC-123 |
2015 |
Production freeze |
| 2020 |
Ban on use in new equipment |
| 2030 |
Ban on production |
| HFC-134a |
|
No restrictions |
Recycled CFCs and HCFCs are not included in the consumption
ban and will continue to be used beyond the ban dates.
Although these dramatic steps pose serious challenges, the purchasers
of commercial air conditioning and refrigeration equipment need
not be excessively concerned. Albeit HCFCs will be phased out,
HCFC22, R500 and 502, and HCFC-123 will be available for sufficient
time to permit orderly transition to acceptable alternate refrigerants.
In addition to the phase-out. the Clean Air Act Amendments required
the Environmental Protection Agency (EPA) to issue mandatory regulations
for the recapture, recycling, and safe disposal of refrigerants.
The amended Act also prohibits venting of CFCs. HCFCs or any other
alternative refrigerants during service, repair, and disposal.
HCFCs (and HFCs with no chlorine at all and no interaction with
ozone) are recognized as absolutely critical to the transition
away from the phased out CFCs. Because they do contribute to ozone
depletion although on a very small scale HCFC refrigerants are
included in the phase-out timetable. The eventual production phase-out
of HCFC123, 22 and other HCFC refrigerants should not be a factor
in deciding which refrigeration equipment to purchase during the
1990s. These refrigerants should be available during the life
of the equipment.
Ozone Depletion Potentials - The relative effect of the
chemicals on the ozone layer is measured by assigning relative
factors, using CFC-11 as the reference. Those without an
atom of chlorine are known as HFCs and have zero ODP. Current
average values of the ODP, as well as the Global Warming Potential
(GWP) and atmospheric lifetimes, for a number of refrigerants
are shown in the following table. These values are averages of
measurements from several different sources. Future additional
scientific data may result in revisions to some of these values.
CFCs and global warming the greenhouse effect - CFCs
have also been implicated in the potential for global warming,
due to their ability to trap heat in the atmosphere. This effect
is another atmospheric phenomenon that is under scrutiny: whether
temperatures on this planet are gradually rising due to incoming
sunlight being trapped by gases, much as cloud cover reduces radiation
cooling at night. Although there are many uncertainties and conflicting
views, there is growing concern in the scientific community that
global warming may be occurring. Carbon dioxide (CO2) is known
to be the main contributor to the Greenhouse Effect, in which
upper atmospheric gases absorb the sun's infrared radiation possibly
causing global warming. Other upper atmospheric trace "greenhouse"
gases (including methane, nitrous oxides [NOx], along with some
CFCs and HCFCs) are also perceived to be linked to the global
warming issue.
The "Greenhouse Effect" has two parts:
- The direct effect of how much infrared radiation is absorbed
by the offending CO2 and trace gases and its effect on the earth's
climate; and
- The indirect effect that relates to energy efficiency. If
the use of a given refrigerant results in even a small increase
in energy consumption over the 20 year or greater life of the
equipment, the impact on global warming is of great concern.
This is due to the added carbon dioxide that would be released
from burning coal or other fossil fuels to supply that extra
energy.
Average Values of Atmospheric
Lifetime, Global
Warming Potential, and Ozone Depletion Potential |
| Compound |
GWP |
Lifetime Years |
ODP |
| CFC-11 |
1.0 |
60 |
1.0 |
| CFC-12 |
3.2 |
120 |
1.0 |
| CFC-113 |
1.4 |
90 |
0.8 |
| CFC-114 |
3.9 |
200 |
0.7 |
| CFC-115 |
7.5 |
400 |
0.4 |
| R-500 |
2.4 |
- |
0.7 |
| R-502 |
5.6 |
- |
0.2 |
| HCFC-22 |
0.34 |
15 |
0.055 |
| HCFC-123 (sub for CFC-11) |
0.02 |
2 |
0.02 |
| HCFC-124 |
0.1 |
7 |
0.022 |
| HCFC-141b |
0.09 |
8 |
0.1 |
| HCFC-142b |
0.36 |
19 |
0.065 |
| HFC-125 |
0.58 |
28 |
0 |
| HFC-134a (sub for CFC-12) |
0.26 |
16 |
0 |
| HFC-143a |
0.74 |
11 |
0 |
| HFC-152a |
0.03 |
2 |
0 |
Most alternative refrigerants are not "drop in" substitutes.
Research and development are resulting in some additional substitutes,
such as R507 and R404A as replacements for R502. HCFC22 (which
is widely used in the United States and elsewhere) is the predominant
refrigerant used in screw, scroll and reciprocating equipments
(and in virtually all unitary equipment). Potential replacements
include R134a, R407C and R410A. Currently, there is no clear substitute
for HC1:4C123.
Conventional Refrigerants - Although CFC11 and 12 production
has been phased out, commercial refrigeration and air conditioners
can continue to use them for many years. As new servicing and
leak repair practices reduce CFC losses, less refrigerant will
be needed to keep present equipment in operation. Also, the recovery,
recycling and reuse of CFC refrigerants from operating and retiring
equipment has become routine practice, extending the supply of
these refrigerants well beyond the 1990s.
Environmentally Acceptable Refrigerants Are Now Available
Alternative refrigerants have been developed that can replace
CFC refrigerants with only slight changes in equipment design
and minimal effects on efficiency. The current principal refrigerant
substitutes are shown in the following table. Several types of
blends are being investigated in order to optimize performance
while providing zero ozone depletion potential.
| Principal Refrigerant Substitutes |
Present
Refrigerant |
Substitute Refrigerant |
| Short Term |
Long Term |
| CFC-11 |
HCFC-123 |
HFC-245ca and other mixtures |
| CFC-12 & R-500 |
HFC-134a |
HFC-134a |
| HCFC-22 |
HCFC-22 |
HFC-134a, R-407C, R-410A, other blends of HFC-32, HFC-134a,
and other components |
| R-502 |
HCFC-22 |
HFC-125, R-507 and other blends of HFC-32, HFC-125, HFC-134a,
and other components |
| CFC-114 |
HCFC-124 |
|
HCFC22 - This HCFC has only about one-third the GWP and
only a small fraction of the ODP of CFC 11, as shown in the table.
Much of the existing pool of knowledge supports the position that
HCFC22 is part of the near term (transition) solution. However
HCFC22 is currently included in the HCFC phase-out provisions.
No health or safety issues have been identified and buyers of
HCFC22 equipment can be assured of its continuing availability
for the expected life of the equipment as HCFC22 will be produced
in declining amounts from 1996 until 2030.
Refrigerant Prices - Rising prices for the present CFC
refrigerants can be expected, considering their decreasing availability
and increasing tax rate. Because of their environmental impact,
the U.S. government has imposed federal taxes on fully halogenated
CFCs. The excise tax on CFCs and halons is ODP weighted. The tax
is applicable only to Class I compounds, which include the five
CFCs listed. No one is sure how expensive substitute refrigerants
will be over time. With the incremental taxes, the price of the
CFC alternatives HFC134a and HCFC123 is now equal to or less than
the rising CFC-12 and 11 prices.
To put this issue in perspective, consider this example. Assuming
a 4% loss of charge per year, and 2 pounds of refrigerant per
ton capacity at a cost of $7.00/lb, the refrigerant cost is $0.56
ton/year of refrigeration design capacity. When compared with
installed costs, and annual maintenance and energy costs, the
refrigerant cost represents a small part of refrigeration equipment
ownership costs. In any event it can be expected that whatever
refrigerant is used the price will be higher than it has been
in the past.
Back to Top
Brine Systems
Brine systems are typically used where temperatures below 32�F are
required and it is not desirable to circulate a direct refrigerant
(R-22, R-502, ammonia, etc.).
A brine system is rarely used in commercial refrigeration applications.
Brine systems use a high concentration of salt water or other
anti-freeze solution which is chilled, then pumped around to do
the required cooling. The common brines used for refrigeration
are sodium chloride (common salt), calcium chloride and various
glycol solutions.
A brine system's advantages are that all refrigeration equipment
is in the engine room directly under the supervision of the engineer,
and that a leak in any other part of the building will leak only
brine (causing considerably less damage and repair costs than
a refrigerant leak). Its biggest disadvantages are that it usually
consumes more energy to maintain a required temperature, and the
brine may be corrosive.
Back to Top
Refrigeration System
Selection
Refrigeration system engineering factors include:
- Year round operation regardless of outdoor ambient (including
low temperatures in winter), wide load functions in short time
intervals, i.e., maintaining total refrigeration availability
while the load varies from 0% to 100%,
- Frost control for continuous performance applications,
- Variations in the affinity of oil for refrigerant caused by
large temperature changes, and oil migration outside compressor
crankcase,
- Choice of cooling medium: (1) direct expansion refrigerant,
(2) gravity or pump re-circulated or flooded refrigerant, or
(3) secondary coolant (brines such as salt and glycol)
- System efficiency and maintainability,
- Type of condenser: air, water or evaporatively cooled,
- Compressor design: - open, hermetic, semi-hermetic motor drive;
reciprocating, screw or rotary,
- System type: single stage, single economized, compound or
cascade arrangement,
- Refrigerant choice: Type of CFC, HCFC, or HFC refrigerant
is primarily selected based upon operating temperature and pressures.
While ammonia is the most common refrigerant for large industrial
applications, it is not used for most commercial refrigeration
due to toxicity.
Based on these and related factors, refrigeration engineers select
suitable standard components or custom fabricated components for
the particular application.
Back to Top
Refrigerant Selection
As the vital working fluid in a refrigeration system, the refrigerant
is selected to provide the best refrigeration effect at a reasonable
cost.
The following characteristics are desirable:
- Nonflammable (to reduce the risk of fire hazard),
- Nontoxic (to reduce potential health hazards),
- Large heat of vaporization (to minimize equipment size and
refrigerant quantity),
- Low specific volume in the vapor phase (to minimize reciprocating
and screw type compressor size),
- Low liquid phase specific heat (to minimize heat transfer
required when sub-cooling liquid below
condensing temperature),
- Low saturation pressure required at desired condensing temperatures
(to eliminate requirement for
heavy duty or high pressure equipment),
- The low pressure portion of cycle should be above atmospheric
pressure (to prevent inward leakage
of air and water vapor into refrigerant piping), and
- High heat transfer coefficients.
The ASHRAE Fundamentals Handbook lists the standard designations
for all refrigerants, including properties, toxicity and flammability.
Each refrigerant is assigned a refrigerant number characteristic
of its chemical structure. Refrigerants commonly used in commercial
refrigeration applications include CFC-12, HCFC-22, CFC-500 and
502. R-12 (CFC-12) has been used for many years in medium-temperature
applications including meat, dairy and product refrigerators and
coolers as well as preparation areas. R-502 (CFC-502) has been used
in low-temperature installations including frozen food and ice cream
refrigerators and walk-in coolers.
Safety Classification of Refrigerants
All refrigerants have an allowable exposure limit (AEL) and threshold
limit value (TLV). Heavier-than-air refrigerants can concentrate
at floor levels and displace breathable oxygen. In ASHRAE Standard
15-1992, 7.4 System Application Requirements specifies the allowable
limits on refrigerant amounts.
ANSI/ASHRAE Standard 34-1992R defines the safety groups. The
table below illustrates the grouping of a number of popular refrigerants.
| Flammability Classification |
|
Toxicity Group |
| Group A |
Group B |
| Lower Toxicity |
Higher Toxicity |
| 3 |
Higher
Flammability |
| A3 - |
Methane |
| |
Propane |
| |
Butane |
|
B3 |
| 2 |
Lower
Flammability |
A2 - HCFC-142b HFC-152b |
B2 - Ammonia |
| 1 |
No Flame
Propagation |
A1 - CFC-11,
-12 CFC-113,
-114 R-500, -502 HCFC-22
HFC-134a |
B1 - HCFC-123 |
ASHRAE Standard 15-1992 - Safety Code for Mechanical Refrigeration
- specifies maximum permissible quantities of refrigerants. From
a safety-monitoring standpoint, the refrigerant amount is unlimited
when, along with other requirements, detectors are located in
areas where refrigerant vapor from a leak is likely to concentrate
to provide an alarm at the following levels:
Safety Group A1 (>400 ppm TLV low toxicity) refrigerants, such
as HFC-134a and HCFC-22, alarms should provide warning at below
19.5% volume oxygen. Safety Group B1 (higher toxicity) refrigerants,
such as HCFC-123, alarms should provide warning at no higher than
their TLV (or toxicity measure consistent therewith).
With HCFC-123, due to its lower AEL and TLV (currently 10 ppm
AEL and TLV) than conventional refrigerants, adequate equipment
room ventilation must be verified.
HCFC-123
HCFC-123 is an environmentally acceptable alternative to CFC-11,
having only a small fraction of the ODP and GWP of CFC-11. The
B1 safety classification of this refrigerant is reflected in ANSI/ASHRAE
Standard 34-1992. The B1 classification requires certain monitoring
(ASHRAE Standard 15-1992) and this should be considered in connection
with its use. In mid-1991 one manufacturing, duPont, reduced the
allowable exposure limits from 100 to 10 parts per million (ppm),
based on preliminary toxicology results. According to duPont's
experience, typical worker exposure during servicing has not exceeded
8 ppm.
Refrigerants that are highly toxic or flammable are not recommended
for commercial use where people may be present.
Note: R-500 and R-502 are azeotropic mixtures of two refrigerants,
one of which is a CFC. As the manufacturing of all CFCs is now
phased out, these two refrigerants are in increasingly short supply.
Back to Top
Compressor Selection
The most common type of compressor used for commercial refrigeration
systems is the reciprocating compressor of either the open, hermetic
or semi-hermetic type.
Reciprocating compressor designs include:
- Single-stage (booster or high stage)
- Internally Compounded
Back to Top
Condenser Selection
Common types of refrigerant condensers for commercial refrigeration
use are:
Water Cooled Evaporatively Cooled Air Cooled
- - shell and tube - Blow-through - Horizontal air-flow
- - shell and coil - Draw-through - Vertical air-flow
- - tube in tube - Static or forced air-flow
The type of condenser selected depends largely on those considerations:
- Size of the cooling load
- Refrigeration used
- Quality and temperature of available cooling water (if any)
- Amount of water that can be circulated, if water use is acceptable
Water cooled condensers are used with cooling towers or ground water
(well, lake, river, etc.).
Back to Top
Typical Use Characteristics
of Refrigeration
The food sales and food service consumers represent the majority
of the refrigeration applications: Food sales consumers are typically
grocery stores, meat markets, delicatessens, supermarkets, and food
lockers. Food service situations are restaurants, cafes, drug stores
serving food, taverns, grills, tea rooms, cafeterias, dining rooms,
carry-out's, delicatessens, and stadium concession stands.
Other common refrigeration uses are for beverage cooling at
taverns, bars, service stations, offices, employee break rooms,
water cooling in offices, stores, service establishments, public
buildings recreation area, and theaters, and ice making such as
cube and block ice for retail sales, fresh food display and as
a hotel/motel amenity.
In addition, refrigeration is commonly used in institutions,
hotels, hospitals, schools, and in special applications such as
cold storage for such products and applications as flowers, medicines,
candies, fresh fruits and vegetables, photo processing, laboratory
supplies, fishing bait, and morgues.
Back to Top
Refrigerator Types
The reach-in refrigerator is found in most establishments that serve
food. Size varies from 10-75 cubic feet; (avg. 50 cubic feet). In
order to satisfy demand for more refrigerator space, the walk-in
refrigerator is often specified. The size of a walk-in refrigerator
is from 175-2500 cubic feet (avg. 500 cu ft).
Bulk dispensing of refrigerated products represents an accepted
use of specialized refrigeration equipment. These units are desired
and accepted by the consumer and owner (e.g., the milk dispenser).
At the same time the owner receives a greater profit on each glass
dispensed than by carton or bottle method.
Back to Top
Food Service Establishment
Refrigeration Guidelines
The average person consumes 2 pounds of food at one sitting (solid
and liquid items). About 1-1/2 cubic feet of refrigerator volume
per person served is a good starting point when determining refrigeration
requirements. A reach-in refrigerator using wire shelves should
normally be loaded to 60% volume capacity. Accessories such as pan
and tray slides can increase usable space to 90%.
Foods requiring separate refrigeration are fish, bakery products,
beverages and ice cream. Storage temperatures:
- Frozen Foods -20�C to 0�F
- Ice Cream -10 to -15�F
- Fish & Shellfish 23 to 30�F
- Meat & Poultry 30 to 38�F
- Dairy Products 38 to 46�F
- Fruits & Vegetables 44 to 50�F
For more details on recommended food refrigeration practices for
various products, refer to the 1994 or later edition of the ASHRAE
Refrigeration Handbook.
Back to Top
Ice Makers
Ice makers produce ice in various shapes and forms. Advantages of
on-site automatic ice makers are in savings (an ice maker can pay
for itself out of savings from cost of purchase and delivery), convenience
(no waiting for deliveries or time wasted chipping and cracking),
sanitation (since ice is normally untouched by human hands), and
being automatic (unattended units shut off when bin is full).
Back to Top
Energy Consumed in Ice
Making
Electric consumption of an ice maker depends on water supply temperatures.
Contact the water company for the average temperature of water in
your area.
| Temperature of Water |
60°F |
65°F |
70°F |
75°F |
80°F |
| Energy: kWh/100 lbs of ice |
5.35 |
5.54 |
5.75 |
5.99 |
6.25 |
|
| Typical Ice Consumption |
| Type of Establishment |
Approximate Ice Needs |
| Hotels & Motels: |
|
| Room Service |
5 lbs per room per day |
| Cocktail Lounge |
3 lbs per person served |
| Food Service |
1-1/2 lbs per person per day |
| Banquet Service |
1 lb per person per day |
| |
| Restaurants |
1-1/2 lbs per person per day |
| Carryout Food Service |
8 oz per 12-16 oz beverage |
| 4 oz per 7-10 oz beverage |
| Cafeterias |
2 lbs per person per day |
| Hospitals |
10 lbs per bed per day |
| Nursing Homes |
6 lbs per bed per day |
Back to Top
Operation and Maintenance
of Refrigeration
Proper operation of the refrigeration plant maintains required temperatures
and moisture levels. This is automatically controlled in commercial
systems. Some attention is occasionally required by the user to
readjust temperatures slightly to defrost coils, and to start and
stop units when required. Safety controls are set to react as appropriate
and protect the equipment from damage in the event of malfunction
or component failure. Since system failure can be both expensive
and dangerous, particularly where food or other product spoilage
is involved, there should also be an on-going, well planned and
executed preventive maintenance program.
Back to Top
Refrigeration Load Considerations
The designer must consider all aspects of the load, including all
items contributing to it, to properly design the refrigeration system.
The following factors must be considered (even though they may not
be involved in the final load):
- Heat leakage (in the form of latent and sensible heat) flowing
into the space or product to be refrigerated,
- Product load: the heat that must be extracted to change the
product's initial temperature to the desired end temperature,
including pull-down time allowable, and the
- Internal sensible load: results from motors, lights and other
heat-generating equipment in the conditioned space impacting
the refrigeration load.
Pull-down time is the length of time it takes to change all of the
product's temperature from the initial temperature going into the
refrigerator to the desired end temperature. If the pull-down time
is too long, some spoilage or discoloration can occur. Excessively
short pull-down times waste energy as the refrigerant's evaporating
temperature is lower than it needs to be.
Process refrigeration loads, while influenced to a certain degree
by these same factors, are dictated mainly by production requirements
(unless thermal storage techniques are used).
Back to Top
Defrosting Refrigeration
Systems
Any evaporator surface operating below 32�F collects frost. Unless
some provision is made to remove it, frost builds up and acts as
an insulator, thereby increasing operating cost. In fact, frost
has an insulating value up to 50 percent of that of cork! Prevention,
defrosting, or periodic removal are common methods used to solve
the frost problem. Defrost cycles are also common in situations
above freezing temperatures where the coil operates below freezing
at some point during the running cycle, and thereby collects frost.
One common defrost method here is to blow the room air (which is
above 32�F) over the coil to melt the frost when the compression
cycle is off.
Commercial and domestic equipment use some form of automatic
control to operate the defrost cycle. Common frost prevention
and defrosting methods used with commercial systems are hot gas
and electric heater systems. Hot gas defrost uses the hot discharge
(high pressure) gas directly from the compressor piped to the
evaporator with a control valve to begin and end the defrost cycle
. Electric heaters are commonly used to defrost domestic and commercial
evaporators. Although the cost of the electricity to operate these
heaters may be appreciable, defrosting is sure and rapid. Always
check the scheduled operating time for these heaters to be sure
they only operate as long as necessary.
Back to Top
Moisture in Refrigeration
Systems
Refrigeration systems are very sensitive to moisture in the refrigerant
side of the system.
If moisture gets into the system, failure may occur due to:
- Ice formation in expansion valves, capillary tubes or evaporators,
- Corrosion of metals,
- Copper plating,
- Chemical damage to insulation in hermetic compressors or other
system materials.
Sources of moisture in the refrigeration system include:
- Faulty equipment drying in factories and service operations,
- Introduction of moisture during installation or service operations
in the field,
- Low-side leaks (resulting in entrance of moisture-laden air),
- Leakage of water-cooled condenser,
- Oxidation of certain hydrocarbons of oil to produce moisture,
- Wet oil, refrigerant or both,
- Decomposing cellulose insulation in hermetically sealed units.
Back to Top |